Abstract

An upgrade of the cryogenic control system for superconducting radio-frequency (SRF) modules of the Taiwan Light Source (TLS) has been completed. The biggest challenge was to recover all protection and operational functions, while minimizing the quantity of vented helium from SRF modules while replacing valve controllers. Gradually, this work was finished within several one- and ten-day scheduled machine shutdown periods for accelerator maintenance. No large helium vent nor pollution of the cryogenic system occurred during all component replacements and function verifications. Functions of the cryogenic electronics were improved, whereas the valve controllers are upgraded to new versions to increase reliability and availability. Communications with the data acquisition system was also secured by buffered signal processing module so that device shutdown of the data acquisition system will not interrupt the cryogenic valve operation.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.