Abstract

This paper presents the application of Genetic Algorithm (GA) and Differential Evolution (DE) technique for the minimization of transmission loss and simultaneous reduction in the operating cost of the system using Flexible AC Transmission System (FACTS) devices. Three types of FACTS devices, Thyristor Controlled Series Compensator (TCSC), Static VAR Compensator (SVC) and Unified Power Flow Controller (UPFC) are considered for this purpose. Optimal placement of FACTS devices in the heavily loaded power system reduces transmission loss, control reactive power flow, improves voltage profile of all nodes and also reduces operating cost. The system is reactively loaded starting from base to 200% of base reactive load and the system performance is observed without and with FACTS devices. The proposed technique is applied on IEEE 30-bus system for the optimal setting of FACTS devices. Finally, how system performance is improved with the use of UPFC along with other series and shunt FACTS controller is illustrated.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.