Abstract

This paper outlines the extension of harmonic domain modeling to flexible ac transmission system (FACTS) devices which contain series voltage injection elements. The proposed iterative technique is capable of modeling generic combinations of series and shunt converters; representing these elements as harmonic current and voltage sources, respectively. The harmonic performance of these converter combinations is characterized in terms of dc current mismatches, which are combined with fundamental frequency power-flow mismatches in an iterative Newton solution. This combination maintains modularity, allowing multiple converter FACTS devices, such as the unified power-flow controller (UPFC), and/or systems containing multiple FACTS devices to be studied. The proposed technique has been successfully validated against time-domain simulation for the UPFC and then used to highlight converter interactions within a UPFC.