Abstract

Three human test series were conducted to evaluate the uniformity of the thermal environments in a stratum-ventilated chamber with dimensions of 8.8m (L)×5.1m (W)×2.4m (H). In all, nineteen conditions were generated by adjusting the room temperature, supply airflow rate, and supply terminal type. An air diffuser performance index (ADPI) of at least 80% was achieved for most cases. This result shows that the air velocity and temperature in the occupied zone are reasonably uniform. Subjective assessments using the ASHRAE 7-point scale indicate that the thermal sensations of the subjects in stratum ventilation are also uniform. This study examines the applicability of the predicted mean vote (PMV) model for evaluating stratum ventilation. When compared to the actual mean thermal sensation votes (ATS), the PMV values are acceptable. The PMV results at a height of 1.1m above the floor show better agreement with the ATS than at a height of 0.1m.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.