Abstract

In this paper, three models of the unified power flow controller (UPFC) suitable for three-phase power flow analysis in polar coordinates are presented. The symmetrical components control model can be used to control the positive-sequence voltage of the shunt bus and the total three-phase active and reactive power flows of the transmission line while the injected shunt voltages and the series voltages are balanced, respectively; the general three-phase control model can be used to control the three shunt phase voltages and the six independent active and reactive power flows of the transmission line; the hybrid control model can be used to control the positive-sequence voltage of the shunt bus and the six independent active and reactive power flows of the transmission line. The proposed UPFC models were successfully implemented in a three-phase Newton power flow algorithm in polar coordinates. In the implementation of these UPFC models, transformers of some common connection types, which connect the UPFC with the network, are explicitly represented. Numerical results based on a five-bus system and the modified IEEE 118-bus system are given to illustrate the UPFC control models and demonstrate the computational performance of the three-phase Newton power flow algorithm.