Abstract

AbstractThe major cause of failure of DC‐GIS is due to presence of foreign particles causing partial discharges in the insulation structure. The particle movement in gas insulated system (GIS) radiates electromagnetic waves and the bandwidth of the signal lies in the range 1–2 GHz. Increase in applied DC voltage/pressure has not altered the frequency content of the ultra high frequency (UHF) signal generated due to partial discharge formed by particle movement. The UHF sensor could recognize the breakdown of sulfur‐hexa‐fluoride (SF6) gas under DC and Lightning impulse voltages and the frequency content of the signal captured by the UHF sensor lies up to 500 MHz. Mounting UHF sensor in GIS could allow one to classify internal partial discharges from breakdown, at the time of testing/during operation. Copyright © 2009 John Wiley & Sons, Ltd.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call