Underside corrosion of a failed above ground storage tank (AST) was investigated by the physio-chemical analysis of water sample that was ingress between the tank bottom plate and the concrete foundation. The results of the water sample analysis showed pH (5.8), temperature (30°C), Conductivity (4800 μs/cm), dissolved oxygen (3.5mg/l), chloride (674mg/l), carbonate (16.90mg/l) and nitrate (23.10mg/l). The levels of the parameters studied were generally high and above statutory safe limits. The results showed that the physico-chemical characteristics of the water sample have diagnostic and predictive values to implicate and promote underside corrosion of the studied above ground storage tank. Journal of Applied Sciences and Environmental Management Vol. 9(1) 2005: 161-163

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.