Abstract
Icing of overhead ground wires on transmission lines may result in faults and widespread power outages. This paper investigates the feasibility of an unconventional overhead line structure that is equipped with underground rather than overhead ground wires to prevent faults caused by icing. The underground ground wire is a buried bare conductor connected to the grounding of each transmission-line tower. To analyze the ground fault of the overhead line structure, this paper derives analytical equations to evaluate the current and potential distribution in the underground ground wire, earth surface potential around the wire, and grounding impedance of the faulted tower. The validity of the presented equations is verified by measurements. Based on the ground fault analysis, this paper evaluates the electrical safety of the discussed overhead line structure. Lightning shielding of overhead lines is not considered in this paper.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.