Abstract

Overhead lines can be replaced by high temperature low sag (HTLS) conductors in order to increase their capacity. The coefficients of thermal expansion (CTE) of the HTLS conductors are lower than the CTE of conventional conductors. The utilities and conductor manufacturers usually carry out the verification of the CTE of the overhead conductors in an actual size span. The verification is based on the observation of the change of the conductor length as a result of the conductor temperature change. This process is influenced by the coefficient of thermal expansion to be verified. However, there are other factors that also affect it. This paper analyzes the effect of some of the uncertainty sources in the testing of the coefficient of thermal expansion of the overhead conductors. Firstly, the thermal expansion process is described and the uncertainty sources related to the conductor and the line section are identified. Then, the uncertainty sources and their effect on the CTE testing are quantified.

Highlights

  • Overhead lines can be replaced by high temperature low sag (HTLS) conductors in order to increase their capacity without the need to reinforce the towers [1]

  • This paper presents the results of the first analysis towards the quantification of the effects of the uncertainties in the testing of the coefficients of thermal expansion (CTE) of overhead conductors

  • The objective of the study is to quantify the effect of these uncertainties so that they are identified as important uncertainty sources or sources that can be neglected

Read more

Summary

Introduction

Overhead lines can be replaced by high temperature low sag (HTLS) conductors in order to increase their capacity without the need to reinforce the towers [1].The conventional conductors work at lower temperatures than HTLS conductors, and their coefficients of thermal expansion (CTE) are higher than the CTE of the HTLS conductors [2,3].CIGRÉ has written a guide providing suggestions for methods and testing for qualifying HTLS conductors [4]. Overhead lines can be replaced by high temperature low sag (HTLS) conductors in order to increase their capacity without the need to reinforce the towers [1]. The conventional conductors work at lower temperatures than HTLS conductors, and their coefficients of thermal expansion (CTE) are higher than the CTE of the HTLS conductors [2,3]. CIGRÉ has written a guide providing suggestions for methods and testing for qualifying HTLS conductors [4]. The low sag performance of HTLS conductors is due to a lower thermal expansion of the conductor. The CTE value of the strands can be determined by tests that are carried out according to certain standards [5,6,7]

Objectives
Results
Conclusion

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.