Abstract
Unbalance load compensation for an electrolytic capacitor-less converter/inverter of the flywheel long life uninterruptible power supply which rating of 3 phase, 200V and 5kW-1min is described. The compensation has following characteristics.(1) Automatic output voltage balancer to cancel output voltage offset and output unbalance of 3 phase inverter.(2) An input negative phase sequence current controller to compensate input current harmonic distortion at unbalanced loads.(3) Automatic gain control on converter to improve input currents and transient states.The UPS has excellence test results which are obtained such as total harmonic distortion THD of input current of 1.2% and 2.0% at 2.6kW single phase load and single rectifier load, respectively. Output voltage offset and unbalance are compensated by automatic output voltage balancer under 0.5s.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.