Abstract

During the past decade the PD probing in the ultra-high frequency (UHF) range has successfully been proven for on-site PD diagnostics of GIS cable terminations in service. Therefore it was decided to apply this non-conventional method also for condition assessment of the insulation integrity of outdoor cable terminations. In order to evaluate the minimum detectable PD level the paper deals with comparative PD studies using the IEC and the UHF method. Moreover, experimental studies on the attenuation of PD pulses traveling through power cables were performed in order to assess the spatial selectivity of the UHF method applied.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.