Abstract

The demodulation method of optical fiber sensors utilized in power transformer partial discharge (PD) detection is insufficient for engineering applications. We design a distributed feedback fiber laser (DFB-FL) PD detection system with an asymmetric 3 × 3 coupler and propose an ultra-high signal-to-noise ratio (SNR) demodulation scheme by eliminating the main factors that affect the traditional method using an asymmetric 3 × 3 coupler. The power transformer PD detection results reveal that the proposed scheme is free from 3 × 3 coupler asymmetry issues, with an average SNR of 38.30 dB, which is much higher than the widely used demodulation method and the piezoelectric transducer sensor. The average SNR of the system is increased by 24.2 dB with the proposed method.