Abstract

Two-phase pressure drop during flow boiling of water in a vertical channel with cross-section 2 mm by 1 mm was investigated experimentally. The experiments were performed for the conditions of heat flux from 25 to 105 kW/m 2, mass flux from 57 to 211 kg/m 2s and exit quality from 9% to 30%, including the influence of inlet compressibility. The two-phase pressure distribution along the channel was recorded at 200 Hz sampling frequency. The results were compared with four correlations. The Lockhart–Martinelli correlation for pressure drop in large tubes with modified C value has been shown to be still applicable with uncertainty of 35%. The homogeneous model had an uncertainty of 50%; the Tran and Chisholm methods over-estimated the experimental data by 100% and 300% respectively. It is shown that none of these correlations can predict published pressure drop data for water during flow boiling in a 50 by 70 micron channel.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.