Abstract

Two-phase flow pressure drop measurements were made during a phase-change heat transfer process with three refrigerants (R-134a, R-12, and R-113) at six different pressures ranging from 138 to 856 kPa, and in two sizes of round tubes (2.46 and 2.92 mm inside diameters) and one rectangular channel (4.06 × 1.7 mm). The data were compared with those from large tubes under similar conditions, and state-of-the-art correlations were evaluated using the R-134a data. The state-of-the-art large-tube correlations failed to satisfactorily predict the experimental data. The data were used to develop a new correlation for two-phase pressure drop during flow boiling in small channels. The correlation was then tested against the experimental data for the three refrigerants; the error was ±20%.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call