Abstract

An experimental study was conducted on a 19.05 mm (outer diameter) dimpled enhanced tube to evaluate the in-tube two phase heat transfer and pressure drop performance in an annular section created between the enhanced tube and a solid round PVC rod. The purpose of the study was to understand the effect of forced early transition to annular flow on the pressure drop and heat transfer coefficient in a horizontal tube. The refrigerant studied was R-134a at a saturation temperature of 5 °C, heat flux range 2.5 to 15 kW m−2, mass flux from 80 to 200 kg m−2 s−1 and inlet vapor quality of 0.12 to 0.72. Flow pattern and pressure drop results were obtained under adiabatic conditions. Under similar operating conditions the enhanced tube with a rod exhibited three times higher heat transfer performance versus same size smooth empty tube with lower pressure drop penalty at lower mas flux.