Abstract
Vapor compression systems in hot climates tend to operate at higher pressure ratios, leading to increased discharge temperatures, higher irreversibilities during compression, lower specific enthalpies differences across the evaporator, and possibly a reduction in the compressor life due to the breakdown of the oil. To counter these effects, the use of economized, vapor injection compressors is proposed for vapor compression systems in high temperature climates. Such compressors are commercially available however an accurate method for mapping single-port injection compressors is unclear. This paper establishes compressor maps for a single-speed R-407C scroll compressor with two-phase injection and vapor-injected compression. A dimensionless-PI correlation for mapping the injection ratio, refrigerant discharge temperature, compressor power consumption, overall isentropic and volumetric efficiencies, and the heat loss ratio for these compressor maps and a variable speed R-410A compressor with vapor injection is presented. The mapping results are compared to the AHRI 10-coefficient polynomial and another proposed correlation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.