Abstract

This paper is the first of two papers that present the result of a study of turbulent flow and pressure drop in a horizontal tube with strip type inserts. Experimental data taken for air for a class of strip type inserts (longitudinal, LS and cross, CS inserts) used as a tube side heat transfer augmentative device for a single-phase cooling mode operation are presented. To broaden the understanding of the underlying physical phenomena responsible for the heat transfer enhancement, flow mechanisms through velocity measurements are combined with pressure drop measurements to develop friction factor correlations for 6500⩽Re⩽19 500 where Re is the Reynolds number. Friction factor increases were typically between 1.1 and 1.5 from low Re(≅6500) to high Re(≅19 500) with respect to bare tubes.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.