Abstract

Usage of enhanced tubes in electric utility steam condensers have many advantages including smaller condenser size, additional electricity generation by lowered condenser back pressure, etc. In the present study, titanium corrugated tubes were tested for application to electric utility steam condensers. The tubes have relatively small corrugation heights and large corrugation pitches. In addition, the lowest helix angle is 18o, which is much lower than those of existing studies. The friction factor increased as corrugation pitch decreased and corrugation height increased. The penalty factor ranged from 1.09 to 1.89. The heat transfer coefficients showed similar trend with that of the friction factor. The enhancement factor ranged from 1.05 to 1.46. Exiting correlations did not adequately predict the present friction factors and heat transfer coefficients. The reason was attributed to the geometric difference of the present corrugated tubes (large p/e and small e/Di). New correlations were developed, which predicted the present data within ±20 %.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.