Abstract

This paper introduces a new fault location algorithm for radial MV distribution networks employing distributed travelling wave observers. Incipient fault location may reduce the risk of wild or bush fire ignition by faulty MV overhead lines. Some faults can develop over time and may exist for an extended period before the right weather conditions result in a fire. Developing faults will produce travelling voltage waves. The distributed observers are synchronized by global positioning system and use the arrival time differences to locate faults. Modal and wavelet transformation is used to detect and time stamp the travelling wave arrival time by observers. The paper first provides a brief review of fault location technology then describes the Floyd-Warshell algorithm to calculate point to point distance matrix. A travelling wave detection methods and finally the fault location algorithm will be described. Simulation model is developed in EMTP-RV software to illustrate the performance of proposed algorithm based on real network data.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.