Abstract

Inverter-based resources respond differently than synchronous generation sources during power system faults, challenging line protection reliability. To understand the reliability challenges, Sandia National Laboratories and North American Electric Reliability Corporation (NERC) led a collaborative study with four inverter manufacturers (mix of Type 3 Wind, Type 4 Wind, and PV Solar) and two North American protective relay manufacturers. As part of this study, an electromagnetic transients program (EMTP) with “real-code” models representing inverter firmware was used to investigate the protective relay response to faults on the modeled power system with the different inverter types. The currents and voltages obtained from the study were then played back through line relay hardware with settings typical of systems with conventional generation. The protective relays exhibited the expected reliability challenges but provided insight into the behavior of inverter-based resources during power system faults. In this paper, we share some of the challenging cases with the responses of the different line protection schemes. Using insight from the various event records, Part II of this paper shows how relay settings can be modified to obtain a substantial improvement in reliability.