Abstract
Small generators connected through a large impedance and operating in synchronism with a weak utility system are more likely to pull out of step on a large perturbation, i.e. a fault in the utility's system. Under an incident impact, which will be distributed unevenly amongst various machines, every machine will be retarded or accelerated, and undergo damped or divergent oscillations. The paper demonstrates that the small machines are more vulnerable and may fall out of step. This may plunge the entire process plant into a complete power outage on system separation. A case study of two small generating units and the improvements in the transient stability by fast system separation and load shedding is demonstrated.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.