Abstract
Self-healing ability is the basic requirement of smart grid. When a fault occurs, the control system should analysis transient stability on line and offer control measures quickly. This paper presents a fast and accurate transient stability emergency control measure. Based on the wide-area measures system, the sensitivity of critical-machine-unit stability index to controlled parameter is derived, and as one of transient stability constraints, sensitivity equation is incorporated into the nonlinear optimization algorithm to obtain the required emergency control amount. The method is simple and quick; the smallest cutting amount ensures load power supply, the simulation verifies the method’s superiority.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.