Abstract

AbstractThe transient grounding impedance of a gas‐insulated switchgear (GIS) substation was investigated through measurements on a commercial 300‐kV underground substation. Using the results, the transient impedance of the grounding grid was investigated. The attenuation factor of the propagation line composed of the outer surface of the GIS tank and the concrete floor was also evaluated. The validity of EMTP analysis of surge phenomena in the GIS grounding system was confirmed. © 2003 Wiley Periodicals, Inc. Electr Eng Jpn, 146(1): 70–77, 2004; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/eej.10214