Abstract

This paper investigates transient recovery voltages across vacuum circuit breakers used for switching mechanically switched shunt capacitor banks in a wind power plant. Simulation case studies are conducted which investigate the transient recovery voltages with the original bank configuration, and a number of modified configurations. It is shown that using the original configuration, with inrush current limiting reactor in series with the capacitor, can result in a breaker failure under most onerous conditions. A number of alternative configurations are proposed which allow management of transient recovery voltages within the breaker withstand level.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.