Abstract

The overvoltage transient characteristics of submarine cables are one of the key technologies for submarine power transmission. This article takes the submarine cable of Zhoushan Multi-terminal Flexible HVDC Transmission Project as the research object. The MMC-HVDC simulation models at both ends of converter stations are built in PSCAD. The parameters and equivalent models of the flexible HVDC cables are determined, and the submarine DC cable operating overvoltage is calculated by using statistical methods. The simulation results show that the maximum overvoltage of the submarine cable, that is, the maximum overvoltage of the conductor to sheath, the sheath to the armour, and the armour to the ground are 400 kV, 7.27 kV and 0.45kV respectively. The maximum overvoltage when it occurs faults on grid-side or valve-side appears in the middle of the submarine cable. Maximum overvoltage of HVDC single pole grounding fault appears at the connection point of land cable and submarine cable. The simulation results and the discovery of features in this article provide reference in the design, selection, and testing of submarine power transmission equipment.