Abstract

This paper proposed a transient numerical model for a coaxial borehole heat exchanger, which considered the impact of borehole specific heat capacity. The fluid vertical temperature distribution inside the coaxial borehole heat exchanger (BHE) had been predicted based on MATLAB and compared with other transient models. Validated by measured data from a thermal response test, the built model agreed better than other models, especially in short times, with a relative error of 3.63% in 2 hours. Then, the quantitative influences of borehole specific heat capacity and other parameters on thermal performance of borehole heat exchangers were specified.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.