Abstract

SUMMARYIn this paper, values of the electric field in the pressboard and oil during the polarity reversal test of the converter transformer were calculated with transient analysis. First, we confirmed the accuracy of the nonlinear analysis in the model test. Next, we carried out nonlinear transient electric field analysis for polarity reversal test of the converter transformer. In the results, when the applied time of dc voltage before the polarity reversal is 360 min, the values of the electric field of oil area are the same as when it is 90 min. Although, the electric field in the pressboard becomes higher in response to the applied time dc voltage, it does not cause a problem on the insulation. Because withstand voltage of pressboard is very high. In the results, the correlation between the applied time of dc voltage before the polarity reversal and the withstand voltage of transformer is considered low. This result can be applied to the design of the converter transformer.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.