Abstract
Previous studies have proposed higher requirements for the transient characteristics of a DC transformer used in a flexible high-voltage direct current (HVDC) system to achieve faster sampling speed and meet wider bandwidth requirements of the control and protection signal, and to eventually suppress the large transient fault current. In this study, a transient characteristics verification method is proposed for transient characteristics verification of a DC transformer used in a flexible HVDC system based on resampling technology and LabVIEW measurement technology after analyzing the key technology for transient characteristics verification of a DC transformer. A laboratory experiment for the transient characteristics of a full-fiber electronic DC transformer is conducted, and experimental results show that such verification method can be employed for frequency response and step response verification of a DC transformer at 10% of the rated voltage and current, and can eventually improve the screening of a DC transformer.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.