Abstract

In this paper, experimental investigations of a two-phase thermosyphon loop are presented in order to keep telecommunication equipments temperature below 55°C. The experimental setup consists of a thermosyphon loop containing an evaporator and a condenser connected by two flexible tubes. Tests are performed firstly in transient state using the thermosyphon loop prototype inside telecommunication cabinet. The n-pentane is used as the working fluid. Firstly, transient thermal characteristics of the thermosyphon loop are measured. In the other way, the thermosyphon loop is tested for different power input up to 450W. Operating temperatures of the telecommunication equipments cooled with forced air convection and two-phase thermosyphon loop are compared.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.