Abstract

A simple and fast method to identify the faulted conductors in a double circuit line with the help of a single circuit transient based fault type classifier is presented in this paper. In addition to a transient based single circuit fault type classifier, only currents locally measured through each conductor are required. Having known the fault type, the magnitudes of the rate of change of currents (ROCOC) through two circuits of faulted phases are compared by calculating three indices to find the conductors involved in the fault. The method can identify faulted conductors during both inter-circuit faults as well as intra-circuit faults. The method can be easily implemented on a simple hardware platform capable of performing filtering and simple mathematical functions. As only the current measurements in the frequency components between 0.5 kHz to 1 kHz are suggested, the need for high bandwidth current transducer is avoided.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.