Abstract

The present paper analyzes the consequences of short grid voltages interruptions on grid-connected self-induction generator, particularly, on the currents and electromagnetic torque of the generator. These effects depend on several variables such as the phase difference between the grid voltages and those of the generator, the magnitude of the grid voltage and the generator currents at the instant of reconnection to the grid. The approach has been used for studying the effects of these grid disturbances on the self-excited induction generator; is a numerical approach. In the numerical approach, which is based on the dynamic d-q model of the induction generator, the effect of magnetic saturation is accurately accounted for. This numerical model has been validated by experimental measurements taken from an induction generator test bench. The analysis focuses on the amplitudes of the peaks of the currents and torque during short interruptions especially at the reconnection of the grid voltage. The results obtained from the numerical model are compared to the measured ones. Full Text: PDF DOI: http://dx.doi.org/10.11591/telkomnika.v16i2.8756

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.