Abstract

Transformer winding deformation is a main type of transformer fault. The Frequency Response Analysis is a effective method to detect transformer winding deformation. Based on the traditional Frequency Response Method, the current source method is a new way to detect winding deformation. This method adopts the current source as sweep frequency source and uses the current frequency response curve to judge winding deformation. The simulation shows that the current source method is feasible. For some special transformers, this method can realize transformer winding on-line monitoring and diagnosis.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.