Abstract
The estimation of voltage transformer tap position is a desirable feature that can be appended to most State Estimation algorithms. The primary requirement to estimate transformer tap position is the availability of a three phase reactive power measurement through either the fixed or tap side of the transformer. These "measured" flows can also be calculated, depending on the availability of reactive injection and reactive transmission line flow measurements around the fixed or tap side buses. The gain matrix of the State Estimator is not modified so only the tables used to calculate real and reactive residual mismatch need to be updated during the State Estimator solution. The computational cost of including transformer tap position estimationis extra iterations of the State Estimator.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.