Abstract

This paper presents experimental validation of the coupled leakage inductance transformer model. It is shown that the coupled approach yields the same results as the indefinite admittance matrix method of BCTRAN. A topologically correct three-phase shell-type transformer model is proposed. The connection points between the leakage and magnetizing inductances are properly identified, which makes the new model superior to BCTRAN and the hybrid models by providing physical consistency. In addition, experimental verification of a method to calculate the short-circuit inductances is presented. New explanations on the division of leakage flux and on the mathematical equivalence between the T- and Π-equivalent models are also given.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.