Abstract

This paper studied the influence of transformer inrush current on commutation failure prevention control of Ultra-high voltage DC (UHVDC) transmission system. An actual event occurred on Tianzhong UHVDC transmission project was analyzed with data from fault recorder. UHVDC transmission model with commutation failure prevention control was established in PSCAD/EMTDC, and then it was applied to replay the event. It is found that the frequent maloperation of commutation failure control and the fluctuation of DC power exist when inrush current occurred. An improved commutation failure prevention control strategy was proposed to avoid this phenomenon. Validity of the improved method was proved by the simulation results.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.