Abstract
Metallic conduits provide mechanical support for cables, and may also protect the cables against interference caused by currents induced by external electromagnetic fields. The conduit transfer impedance Z/sub t/ then is a good measure for the provided protection. We studied Z/sub t/ by means of conformal transformations and of the method of moments in a quasistatic, two-dimensional (2-D) approach. Practical U-, H-, L-, and T-shaped conduits are discussed. Conformal transformations provide simple engineering expressions for the mutual inductance part of Z/sub t/ for cable positions inside the conduit. The method of moments formulation results in useful approximations for the crossover frequencies in Z/sub t/ between DC and high frequency. Measurements on U-shaped conduits confirm the calculations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEE Transactions on Electromagnetic Compatibility
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.