This paper presents a fast and accurate method to determine the available transfer capability. The Ralston's method is used to predict the two trajectory points of voltage magnitude, power flow and maximum generator rotor angle difference. Then, the cubic-spline interpolation technique is used to accurately trace the P-V, P-S or P-Δδ curves between two points of trajectory. The P-V, P-S and P-Δδ curves represent as the variations of voltage magnitude, power flow and maximum generator rotor angle difference due to the increase of power transfer. The actual available transfer capability value is determined at the intersection point between the curve and the constraints limit. The effectiveness of the proposed method is verified utilizes 39-New England bus system. The proposed method gives satisfactorily accurate and fast computation of ATC compared to recursive AC power flow method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.