Abstract

The DC magnetic bias phenomenon in transformers can result in increased noise and harmonic components. This study focuses on the DC magnetic bias generated by stray currents in the DC traction power supply system of neutral grounding transformers under multiple train operation conditions. A two-layer soil model is utilized to calculate geodetic potential, with rail potentials from both mainline and depot serving as sources for stray current within the model. Two paths of stray current intrusion into the transformer via the grounding network and cable armor layer from the Main substation have been modeled and analyzed. A simulation test has been designed to verify that the maximum error between experimental data and model calculation data is 8.87%. The implementation of a blocking connection device between the depot and mainline, as well as a change in grounding strategy for the metal protective layer, can effectively reduce DC bias magnetic current in the substation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.