Abstract

In order to give out inverse V-type insulator tower air-gaps configuration of double-circuit UHV AC power transmission line, different distance air-gaps from high-voltage electrode to tower frame discharge tests of inverse V-string are carried out. Discharge characteristics curves of power frequency voltage, 1000 μs long wave-front switching impulse voltage, and lightning impulse of UHV AC double-circuit tower are obtained. Results show that the 50% discharge voltage gradient of bottom phase air-gaps is higher than middle phase. 1000 μs wave-front switching impulse 50% discharge voltage gradient of bottom phase air-gaps is 4.6% higher than the middle phase. Based on the test results and the characters of operating voltage and overvoltage of UHV AC power transmission system, the UHV AC double-circuit tower inverse V-type insulator air-gaps configuration is proposed. The air-gap configurations of power frequency voltage and switching overvoltage are 2.9 and 6.5 m, and the lightning protection air-gaps are 6.7 and 7.2 m, in mountains and plains.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.