Distributed generation (DG) and solar photovoltaic (PV) systems are just two of the many places multilevel inverters have found a home. The total harmonic distortion (THD) of an inverter's output voltage or current is widely regarded as a useful quality indicator. In order to lessen THD while enhancing the performance of the network, the authors of this research presented a unified controller.An integrated controller consisting of PID (Proportional-Integral-Derivative),Fuzzy,and Artificial Neural Network (ANN) controllers is used in the 31-level multilevel inverter to reduce THD in the PV system. The fundamental frequency of the suggested integrated controller is 50 Hz,and the simulation results show that the THD is reduced to 0.94 percent. The proposed controller's performance shown a considerable decrease in 5th order harmonics for the Cascaded H-bridge Multilevel Inverter,as well as an average percentage reduction in line voltage total harmonic distortion of 17.04 compared to the existing approach.