Abstract
This paper outlines the results of a general transient network analyzer study on a 765 kV circuit to determine the phase-to-ground switching surge overvoltages for a variety of circuit breaker and transmission line conditions. The circuit was modelled after the standard transmission line as specified in ANSI standard C37.071a- 1974. An electronic differential analyzer was used to control the transient network analyzer and to rapidly measure switching surge statistical data. The results are given in terms of curves showing the variation in surge magnitudes with network and circuit breaker parameters including closing span, insertion time, insertion resistance and compensation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.