Abstract
Three industrial-type centrifugal fans were designed, fabricated and tested in order to investigate the effects of axial (tip) clearance between an unshrouded impeller and stationary casing, so that the flow field behavior may differ considerable from that of a shrouded centrifugal fan impeller. Tests were conducted under high temperatures of gas up to 1000 °C at six different values of tip clearance each. Test results showed that the tip leakage flow due to the tip clearance is an unavoidable factor, which deteriorates the fan performance, and therefore the impeller geometry should be designed considering the tip clearance losses.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.