Abstract
This study presents a single-ended fault location method that does not need the information of the remote-end system. As the foundation of the proposed method, the fault location equations under different fault types are derived based on the fault loops. The fault distance, fault impedance, and equivalent resistance and inductance of the remote-end system are considered as the unknowns of the fault location equation. Then the equation can be solved using the Gauss-Newton method, by which the four unknowns can be obtained. Therefore, the proposed method is not sensitive to the fault impedance and the system parameters. A two-terminal 500 kV ac transmission line test system is built in PSCAD to verify the proposed method. Numerous simulation data of faults of different fault distances, fault impedances, and fault types verify the accuracy and robustness of the proposed method. The proposed method is a time-domain method that can locate the fault using 5 ms data after the faults.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.