Abstract

Partial discharge (PD) detection and location is of great significance for the power cable insulation condition monitoring, where analysis of the PD propagation is needed. This paper presents the single-core model of cross-linked polyethylene (XLPE) cable considering the influence of skin effect and semi-conducting screens. To analysis the propagation of PD pulse in time domain, the model firstly is rational approximated using vector fitting method. Based on the fitting results, the π section lumped parameters model is then proposed. Examples on two cables with different permittivity approximating forms of semiconducting screens are presented.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.