Abstract

A time domain method for accurate modeling of external power systems in electromagnetic transients programs (EMTPs) is presented. The time domain response of the external system to a multisine excitation signal is utilized to identify a discrete-time model for the external system. The identified model parameters are determined by least-squares estimation. The details of building both single-phase and multiphase equivalents are given. The validity of the equivalents is verified by comparing the electrical transients generated due to the energization of an open-ended line using the full and the equivalent external system. The method is being extended to multiport equivalents.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call