Calculating the synchronous generator steady state operating conditions and load angle is essential for power system studies. Time and space harmonics can cause variations on power system operation. This paper investigates the impact of time and space harmonics on the synchronous generator inductances, rotor currents, produced stator fluxes and voltages, electromagnetic torque, and the steady state rotor angle. Harmonic domain and abc-frame of reference is used for non-linear modelling of synchronous generators. The instantaneous electromagnetic torque is calculated using rotational voltage component. Simulation results show that the presence of harmonics can affect the synchronous generator steady state operation and damper windings have considerable impact on the produces stator fluxes and voltages in the presence of harmonics. MATLAB/Simulink software and Simpower system toolbox are used for the simulation in time domain.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.