Abstract
A thyristor controlled ground fault current limiting system (TGCL) was proposed to prevent one-line ground fault current rises due to increased capacitance to ground. Basic components of the TGCL are a main ground fault current limiter, which rapidly adjusts a compensating reactor level for the capacitance to ground, and the TGCL's controller. Control is ensured by an in-phase control method for zero-phase sequence voltage and current. The method determines the direction of ground faults and the compensating reactor level. The fast control which can be realized shows the TGCL is a valuable protecting system for high ground fault current distribution systems.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.