Abstract

This paper presents a direct current-space-vector control of an active power filter (APF) based on a three-level neutral-point-clamped (NPC) voltage-source inverter. The proposed method indirectly generates the compensation current reference by using an equivalent conductance of the fundamental component using APF's dc-link voltage control. The proposed control can selectively choose harmonic current components by real-time fast Fourier transform to generate the compensation current. The compensation current is represented in a rotating coordinate system with chosen switching states from a switching table implemented in a field-programmable gate array. In addition, a three-phase four-wire APF based on a three-level neutral-point-clamped inverter is also presented. The proposed APF eliminates harmonics in all three phases as well as the neutral current. A three-phase three-wire NPC inverter system can be used as a three-phase four-wire system since the split dc capacitors provide a neutral connection. To regulate and balance the split dc-capacitor voltages, a new control method using a sign cubical hysteresis controller is proposed. The characteristics of the APF system with an LCL-ripple filter are investigated and compared with traditional current control strategies to evaluate the inherent advantages. The simulation and experimental results validated the feasibility of the proposed APF.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call