Abstract
Conventional dynamic voltage restorers (DVRs) are connected to the power grid through power-frequency transformers. These bulky and costly transformers cause voltage drop and power losses. In this paper, a high-frequency-link dynamic voltage restorer (HFL-DVR) is proposed based on transformer-isolated topologies. This topology facilitates independent operation conditions for each phase in a three-phase system. It enjoys relatively low cost, low losses, and small size. Also, it is free from transformer inrush currents. Small-signal ac equivalent circuit for the power stage including HFL-DVR is derived based on an averaged modeling approach. Transfer functions are obtained to study the effect of inputs such as dc-link voltage, grid voltage, and the load current on the output of HFL-DVR. In order to obtain acceptable properties such as transient overshoot, setting time, and steady-state error, a PID controller is added to the system. This shows that the effect of disturbances on the output of HFL-DVR can be reduced. The experimental results are obtained from a 220V/50Hz HFL-DVR setup. The simulation and experimental results have been compared to verify theoretical aspect of the proposed DVR for both symmetrical and asymmetrical voltage sag conditions.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.