Abstract

Simulations of three-phase faults at the generator terminals have shown the existence of non-zero currents in all three phases for several cycles. Particularly in the application of generator circuit breakers, there could be a serious problem in that the delayed current-zero phenomenon might inhibit normal circuit opening. This investigation was undertaken to develop a method of modeling the circuit breaker arcing characteristics and determine the influence of arc gap resistance on the normal fault current decay. The paper presents the fundamental theory of the non-zero current phenomenon along with the basic operation and modeling of typical air-blast circuit breakers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.